Home > Support > Knowledge Base > Knowledge Base Article

Omron Digi One IA RealPort Ethernet to Serial Gateway

Table of contents: 

        Section 1.  Product Overview
          Section 2.  Hardware Setup
          Section 3.  Wiring
          Section 4.  Software Setup
                                 Part 2.  Installing the RealPort Virtual Com Port for
                                              a. Windows 2000
                                              b. Windows XP
                                              c.  Windows NT

           Section 5.  Tested Omron Products
         Section 6.  Performing a firmware upgrade 

Section 1.  Product Overview

The Ethernet to Serial Gateway is a product that is a combination of hardware and software that enables Omron PLCs, temperature controllers, panel meters and other serial devices that do not have built in Ethernet capabilities to communicate on Ethernet Network.  The protocols that can be used with this converter are HostLink (both C and CV mode) and CompoWay F.  The Digi One IA RealPort gateway can be used for programming, monitoring, data acquisition, etc. 

The hardware component of the Gateway is a DIN Rail mountable DC Powered Ethernet to Serial Converter.  This converter plugs into a plant Ethernet Network with a user defined IP address.  It also plugs into an Omron PLC through an RS232, RS422, or RS485 serial port.

The software component of the Gateway is a Virtual COM Port that runs on the computer that wishes to talk to the PLC, temperature controller, or other serial device.  This Virtual Com Port allows the hardware Ethernet to Serial converter attached to the serial device to appear as a standard Windows Com port to an application such as CX Programmer, FINSGateway, SysConfig, Syswin, or other windows application.


Section 2.  Hardware Setup         

1.      Connect 12 or 24 VDC power to the Power connector on the Digi One IA RealPort.  The polarity is marked on the device. 

2.      Set the DIP Switches as shown for RS232, RS422, or RS485 connections to the Omron device. 

For RS232

Position

1

2

3

4

Setting

On

Off

Off

Off

 For RS422

Position

1

2

3

4

Setting

Off

On

Off

On

For RS485

Position

1

2

3

4

Setting

Off

Off

On

On

3.      Connect the Digi One IA RealPort to the Ethernet network. 

4.      Connect the Digi One IA RealPort to the Omron Device(s) using the cabling diagrams in Section 3: Wiring

5.      Once the cables are connected, proceed to Section 4:  Software Setup.


Section 3.  Wiring 

  a.  For RS232 Connection to Omron PLCs with 9 Pin Serial Port 

b.      For RS232 connection to Omron PLCs with 25 Pin Serial Ports 

c.       For RS422 connection of Omron PLCs using the CPM1-CIF11 RS422 to Peripheral Port converter.  The CPM2C-CIF11 converter is wired identically.

d.  For RS422 Connection to Omron PLCs using CS1W-SCU or CQM1H-SCU41

e.      For RS485 Connection to Omron Temperature controllers and other RS485 devices 


Section 4.  Software Setup

The software setup is divided into 2 parts, configuring the Digi One IA RealPort hardware using Digi RealPort Remote tool, and installing the virtual COM port on the computer(s) that will communicate with the Omron devices using the Ethernet to Serial gateway.

Part 1.  Configuring the Digi One IA RealPort Device 

1.      Install the Digi RealPort Remote software by running Setup.exe on the supplied CD.

 

2.      From the above screen, select your computer Operating System (Currently only Windows NT, 2000, and XP are supported), Hardware (Digi One), and Software (Digi Port Authority - Remote).   Then click Install Software.

 3.      Select the installation location, and click Next. 
      

4.      Select the program folder and click Next.
 

 5.      When the installation is complete, click Finish (leave Launch Digi Port Authority - Remote checked)
      

6.      In the above configuration window, click Discover to allow the Digi Port Authority Remote software to search for the connected hardware. 

7.      The software should report that a device without an IP address has been detected.  Click OK.  If the software did not find the hardware, check the power connection and Ethernet connection to the Digi One RealPort IA device and try the Discover option again.  

8.      In the configuration software, click Configure.

9.      Enter the IP address, Subnet, and Gateway (if applicable) for the hardware.  If uncertain of these parameters, contact your network administrator.  Click OK.  

10.  Wait while the software applies the settings, and tests the device. 

11.  The configuration window will appear again, with the IP address that you entered above in the Device window.  Click Configure. 

         12.  You will be asked for the User Name and Password.  The default User Name is root and the default password is dbps.  Enter these and click OK. 

13.  Your default internet application will take you to a web based setup application that runs on the Digi One IA RealPort.  Select Setup Wizard. 

14.  Select Industrial Protocols

15.  Click Next

16.  Choose the baud rate, data bits, parity, and stop bits to match the Omron device.  Omron default settings for many products are 9600, 7,E,2.  Click Next.  

17.  Select the Omron protocol that you wish to use.  Choose Hostlink for C and CV mode Hostlink , and Compoway/F for the CompowayF protocol.  For Omron PLCs use Hostlink.  Click Next. 

18.   Select Slave.  Click Next. 

19.  Verify the settings that you have made, and click Finish

20.  Click on Admin, and then click Reboot.  Click Continue.  This will restart the module, and apply the configuration changes that you have made.  

This concludes the configuration process for the Digi One IA RealPort hardware.  You can modify any of these changes at any time by launching the Digi Port Authority - Remote software from the start menu, and starting at step 11 of this section.  Please proceed to Part 2. Installing the RealPort Virtual Com Port.                        

Part 2.  Installing the RealPort Virtual Com Port in:
Windows 2000
   1.      From the Control Panel of Windows 2000, Select Add Hardware.  Click   Next.

   2.      Select Add/Troubleshoot a device.  Click Next. Windows will search for new devices. When it determines that it cannot find
          any new devices, it will display a list of devices.

   3.      Select Add a new device Click Next.

   4.      Select No, I want to select the hardware from a list.  Click Next.

   5.      Select Multi-port serial adapters Click Next.

   6.      Select Have Disk.

   7.      Select Browse, and point the system to the \drivers\windows\w2k\RealPort directory on the supplied CD, and select the digirp.inf
         
file.  Click Open.

   8.      Click OK

   9.      Select the Digi One IA RealPort.  Click Next, Next

    10.   If the Digital Signatures Not Found screen appears, click Yes.

    11. Enter the IP address of the Digi One IA RealPort.  Click Next.

    12. Enter a Name to refer to the Digi One IA RealPort.  Enter the number of simulated COM ports you would like to setup for the
           computer that you are using.  Click Next.

   13.  Click Finish 

    This completes the installation of the simulated COM port.  Omron software can now address your Omron hardware device using the
    COM port number that you assigned in step 12.


Windows XP
  
1.      From the Control Panel of Windows XP, Select Add Hardware.  Click Next.

   2.      Select I have already connected the hardware. Click Next.

    3.      Scroll and select Add a new hardware device.  Click Next.

   4.      Select Install the hardware that I manually select from a list. Click Next.

   5.      Select Multi-port serial adapters. Click Next.

   6.      Select Have Disk.

   7.      Select Browse and select the driver location.  From the supplied CD,  drivers\windows\w2k\RealPort

    8.      Select the RealPort driver and Open Click OK.

    9.      Choose the Digi device you are installing Click Next, Next.

    10.  A Hardware Installation warning screen appears, choose Continue Anyway.

   11.  Enter the IP address for the Digi IA RealPort device. The TCP port number should be 771.

   12.  Follow the prompts to complete configuration of the RealPort driver.


For Windows NT
  
1.      From the WindowsNT Control Panel, Double Click Network.

    2.      Click on the Services Tab.

    3.      Click Add.

    4.      Click Have Disk.

    5.      Type the path for the driver.  For example, if your CD ROM is drive D, the path would be d:\drivers\windows\nt\RealPort\.

    6.      Click OK to select the highlighted Digi RealPort Service.

    7.      Enter the IP address for the Digi One RealPort IA.  Click Next.

    8.      Enter a Name to refer to the Digi One IA RealPort.  Enter the number of simulated COM ports you would like to setup for the
    computer that you are using.  Click Next

    9.      Click Finish

    10.  Click OK

    11.  Click Yes to start the RealPort service.

Section 5.  Tested Omron Products

a.  PLCs

CPM1(A)

CPM2(A,C)

CQM1(H)

SRM1

C200H E,G,X

CJ1

CS1

CV

Syswin

YES

YES

YES

YES

YES

YES

CX-Programmer

YES

YES

YES

YES

YES

YES

YES

YES

CPT

YES

YES

YES

YES

YES

YES

CX Server OPC

YES

YES

YES

YES

YES

YES

YES

YES

CX Server Lite

YES

YES

YES

YES

YES

YES

YES

YES

FINS Gateway

YES

YES

YES

YES

YES

YES

YES

YES

DeviceNet Configurator

YES

YES

CX Protocol

YES

YES

YES

YES

CX Motion

 

YES

 

CX Supervisor

YES

YES

YES

YES

YES

YES

YES

YES

b.  Temperature Controllers and other MSC products

E5ZE

E5ZN

E5CK

K3GN

H8GN

E_GN

Sysconfig

YES (1)

YES (2)

YES (1)

YES(2)

YES(2)

 

 1. HostLink Protocol

2. Compoway/F Protocol

c.  Other Products

Product

Comments

NT Series Touch Screens

Cannot communicate.  This is not a supported protocol.

Section 6:  Performing a firmware upgrade.

Periodically, Digi will make updated firmware for the Digi One IA RealPort available.  These updates may include new drivers or updates for existing drivers.  Below is the procedure for applying a firmware upgrade to a Digi One IA RealPort.

1.      Obtain an updated firmware file from Digi or Omron. (.bin file extension)

2.      Using the Digi Port Authority Remote software, connect to the Digi One IA RealPort. 

3.      From the menu on the left, click on Admin

4.      Click on HTTP Upgrade

5.      Click Browse to select the file from step 1. 

6.      Click Submit. 

7.      Wait while the unit downloads the update. 

8.      When prompted, click Reboot.